A load takes 42 kW of real power and 39.5 kvar of reactive power (lagging). Find the power factor cos φ.
AC power & power factor worksheet with answers
A voltmeter, an ammeter and a wattmeter connected to a single-phase inductive load read 120 V, 7.5 A and 720 W. Find the power factor cos φ of the load.
Two loads are connected in parallel to a 240 V single-phase supply: a 14 kW load at a power factor of 0.85 lagging and a 2 kW heater (unity power factor). Find the total current I drawn from the supply.
A load with impedance Z = 4 + j3 Ω is connected to a 240 V (rms) single-phase supply. Find the real power P it absorbs.
A 75 kVA single-phase transformer supplies a load of 21 kW at a power factor of 0.6 lagging. How much extra real power ΔP can be added as a resistive (unity power factor) load before the transformer reaches its kVA rating?
A single-phase load takes 17 kW at a power factor of 0.65 lagging from a 230 V, 60 Hz supply. A 150 µF capacitor is connected in parallel with the load. Find the new power factor cos φ seen by the supply.
Answer key
- 1. cos φ = 0.7285
- 2. cos φ = 0.8
- 3. I = 75.84 A
- 4. P = 9216 W
- 5. ΔP = 48.58 kW
- 6. cos φ = 0.7095
Full step-by-step solutions: practise this topic on examproblems.com.