A single-phase load draws 13 A (rms) from a 400 V (rms) supply at a power factor of 0.9 lagging. Find the reactive power Q it takes.
AC power & power factor worksheet with answers
A load takes 44.5 kW of real power and 50 kvar of reactive power (lagging). Find the apparent power S.
An inductive load takes 12.5 A and 1725 W from a 230 V (rms) single-phase supply. Model it as a resistance R in series with a reactance X. Find X.
Two loads are connected in parallel to a 240 V single-phase supply: a 7 kW load at a power factor of 0.7 lagging and a 15 kW load at a power factor of 0.8 lagging. Find the total current I drawn from the supply.
A single-phase load takes 15 kW at a power factor of 0.8 lagging from a 230 V, 50 Hz supply. A capacitor connected in parallel raises the power factor to 0.95. Find the new line current Inew.
A single-phase load takes 10 kW at a power factor of 0.7 lagging from a 400 V, 60 Hz supply. A 47 µF capacitor is connected in parallel with the load. Find the new power factor cos φ seen by the supply.
Answer key
- 1. Q = 2267 var
- 2. S = 66.93 kVA
- 3. X = 14.72 Ω
- 4. I = 119.5 A
- 5. Inew = 68.65 A
- 6. cos φ = 0.8051