A load takes 43 kW of real power and 39.5 kvar of reactive power (lagging). Find the apparent power S.
AC power & power factor worksheet with answers
A single-phase load draws 11 A (rms) from a 120 V (rms) supply at a power factor of 0.85 lagging. Find the real power P it takes.
An inductive load takes 4 A and 384 W from a 120 V (rms) single-phase supply. Model it as a resistance R in series with a reactance X. Find X.
A single-phase motor takes 6 kW at a power factor of 0.8 lagging from a 240 V supply. Find the line current I.
A 24 V (rms), 60 Hz source has an internal impedance Zs = 25 + j20 Ω. The load impedance ZL can be chosen freely. Find the maximum real power Pmax that can be delivered to the load.
A 150 kVA single-phase transformer supplies a load of 68 kW at a power factor of 0.6 lagging. How much extra real power ΔP can be added as a resistive (unity power factor) load before the transformer reaches its kVA rating?
Answer key
- 1. S = 58.39 kVA
- 2. P = 1122 W
- 3. X = 18 Ω
- 4. I = 31.25 A
- 5. Pmax = 5.76 W
- 6. ΔP = 51.5 kW