A load takes 36.5 kW of real power and 11 kvar of reactive power (lagging). Find the apparent power S.
AC power & power factor worksheet with answers
A load takes 44.5 kW of real power and 49.5 kvar of reactive power (lagging). Find the apparent power S.
Two loads are connected in parallel to a 400 V single-phase supply: a 21 kW load at a power factor of 0.6 lagging and a 17 kW heater (unity power factor). Find the total current I drawn from the supply.
Two loads are connected in parallel to a 400 V single-phase supply: a 9 kW load at a power factor of 0.6 lagging and a 17 kW heater (unity power factor). Find the overall power factor cos φ seen by the supply.
A single-phase load takes 29 kW at a power factor of 0.7 lagging from a 240 V, 60 Hz supply. A 470 µF capacitor is connected in parallel with the load. Find the new power factor cos φ seen by the supply.
A single-phase load takes 12 kW at a power factor of 0.7 lagging from a 240 V, 60 Hz supply. A 470 µF capacitor is connected in parallel with the load. Find the new power factor cos φ seen by the supply.
Answer key
- 1. S = 38.12 kVA
- 2. S = 66.56 kVA
- 3. I = 118 A
- 4. cos φ = 0.908
- 5. cos φ = 0.8314
- 6. cos φ = 0.9859
Full step-by-step solutions: practise this topic on examproblems.com.