A single-phase load draws 3 A (rms) from a 230 V (rms) supply at a power factor of 0.75 lagging. Find the real power P it takes.
AC power & power factor worksheet with answers
A voltmeter, an ammeter and a wattmeter connected to a single-phase inductive load read 120 V, 20 A and 1680 W. Find the power factor cos φ of the load.
Two loads are connected in parallel to a 240 V single-phase supply: a 16 kW load at a power factor of 0.65 lagging and a 26 kW heater (unity power factor). Find the overall power factor cos φ seen by the supply.
Two loads are connected in parallel to a 240 V single-phase supply: a 6 kW load at a power factor of 0.6 lagging and a 17 kW load at a power factor of 0.7 lagging. Find the overall power factor cos φ seen by the supply.
A 100 V (rms), 50 Hz source has an internal impedance Zs = 2 + j15 Ω. The load impedance ZL can be chosen freely. Find the maximum real power Pmax that can be delivered to the load.
A single-phase load takes 15 kW at a power factor of 0.65 lagging from a 240 V, 50 Hz supply. A capacitor connected in parallel raises the power factor to 0.9. Find the new line current Inew.
Answer key
- 1. P = 517.5 W
- 2. cos φ = 0.7
- 3. cos φ = 0.9135
- 4. cos φ = 0.672
- 5. Pmax = 1250 W
- 6. Inew = 69.44 A