A load takes 34.5 kW of real power and 14.5 kvar of reactive power (lagging). Find the apparent power S.
AC power & power factor worksheet with answers
A single-phase load connected to a 120 V supply takes 26 kW and 5.5 kvar. Find the current I drawn from the supply.
A single-phase motor takes 28 kW at a power factor of 0.6 lagging from a 240 V supply. Find the reactive power Q it draws.
An inductive load takes 16 A and 1152 W from a 120 V (rms) single-phase supply. Model it as a resistance R in series with a reactance X. Find R.
A single-phase load takes 20 kW at a power factor of 0.65 lagging from a 400 V, 60 Hz supply. A capacitor connected in parallel raises the power factor to 0.9. Find the capacitance C needed.
A single-phase load takes 25 kW at a power factor of 0.6 lagging from a 240 V, 60 Hz supply. A capacitor connected in parallel raises the power factor to 0.98. Find the new line current Inew.
Answer key
- 1. S = 37.42 kVA
- 2. I = 221.5 A
- 3. Q = 37.33 kvar
- 4. R = 4.5 Ω
- 5. C = 227.1 µF
- 6. Inew = 106.3 A