A single-phase load draws 18 A (rms) from a 240 V (rms) supply at a power factor of 0.85 lagging. Find the reactive power Q it takes.
AC power & power factor worksheet with answers
A single-phase load connected to a 120 V supply takes 27.5 kW and 17.5 kvar. Find the current I drawn from the supply.
A single-phase motor takes 25 kW at a power factor of 0.65 lagging from a 240 V supply. Find the line current I.
A single-phase motor takes 31 kW at a power factor of 0.7 lagging from a 230 V supply. Find the line current I.
A single-phase load takes 29 kW at a power factor of 0.6 lagging from a 230 V, 50 Hz supply. A 330 µF capacitor is connected in parallel with the load. Find the new line current I.
A 10 V (rms), 50 Hz source has an internal impedance Zs = 8 + j3 Ω. The load impedance ZL can be chosen freely. The load for maximum power is built from a resistor in series with a capacitor. Find the capacitance C.
Answer key
- 1. Q = 2276 var
- 2. I = 271.6 A
- 3. I = 160.3 A
- 4. I = 192.5 A
- 5. I = 191.6 A
- 6. C = 1061 µF