A single-phase load draws 2 A (rms) from a 400 V (rms) supply at a power factor of 0.7 lagging. Find the reactive power Q it takes.
AC power & power factor worksheet with answers
A load takes 8.5 kW of real power and 2.5 kvar of reactive power (lagging). Find the apparent power S.
Two loads are connected in parallel to a 230 V single-phase supply: a 26 kW load at a power factor of 0.75 lagging and a 20 kW load at a power factor of 0.9 lagging. Find the total current I drawn from the supply.
A single-phase motor takes 30 kW at a power factor of 0.75 lagging from a 230 V supply. Find the reactive power Q it draws.
A single-phase load takes 15 kW at a power factor of 0.65 lagging from a 400 V, 50 Hz supply. A capacitor connected in parallel raises the power factor to 0.95. Find the capacitance C needed.
A single-phase load takes 7 kW at a power factor of 0.65 lagging from a 240 V, 60 Hz supply. A 68 µF capacitor is connected in parallel with the load. Find the new line current I.
Answer key
- 1. Q = 571.3 var
- 2. S = 8.86 kVA
- 3. I = 245.2 A
- 4. Q = 26.46 kvar
- 5. C = 250.8 µF
- 6. I = 40.39 A