A single-phase load draws 20 A (rms) from a 400 V (rms) supply at a power factor of 0.85 lagging. Find the real power P it takes.
AC power & power factor worksheet with answers
A single-phase load connected to a 240 V supply takes 29 kW and 14 kvar. Find the current I drawn from the supply.
A single-phase motor takes 13 kW at a power factor of 0.75 lagging from a 230 V supply. Find the line current I.
A load with impedance Z = 5 + j12 Ω is connected to a 240 V (rms) single-phase supply. Find the reactive power Q it absorbs.
A single-phase load takes 40 kW at a power factor of 0.6 lagging from a 400 V, 60 Hz supply. A capacitor connected in parallel raises the power factor to 0.95. Find the capacitance C needed.
A single-phase load takes 40 kW at a power factor of 0.6 lagging from a 240 V, 60 Hz supply. A capacitor connected in parallel raises the power factor to 0.98. Find the capacitance C needed.
Answer key
- 1. P = 6800 W
- 2. I = 134.2 A
- 3. I = 75.36 A
- 4. Q = 4090 var
- 5. C = 666.2 µF
- 6. C = 2082 µF
Full step-by-step solutions: practise this topic on examproblems.com.