A single-phase load draws 6 A (rms) from a 120 V (rms) supply at a power factor of 0.65 lagging. Find the real power P it takes.
AC power & power factor worksheet with answers
A load takes 16.5 kW of real power and 6.5 kvar of reactive power (lagging). Find the power factor cos φ.
Two loads are connected in parallel to a 240 V single-phase supply: a 21 kW load at a power factor of 0.85 lagging and a 16 kW heater (unity power factor). Find the total current I drawn from the supply.
A load with impedance Z = 12 + j16 Ω is connected to a 240 V (rms) single-phase supply. Find the apparent power S.
A single-phase load takes 27 kW at a power factor of 0.6 lagging from a 240 V, 60 Hz supply. A 330 µF capacitor is connected in parallel with the load. Find the new power factor cos φ seen by the supply.
A single-phase load takes 9 kW at a power factor of 0.7 lagging from a 400 V, 60 Hz supply. A 47 µF capacitor is connected in parallel with the load. Find the new line current I.
Answer key
- 1. P = 468 W
- 2. cos φ = 0.9304
- 3. I = 163.4 A
- 4. S = 2880 VA
- 5. cos φ = 0.6835
- 6. I = 27.53 A