A load takes 39 kW of real power and 11 kvar of reactive power (lagging). Find the apparent power S.
AC power & power factor worksheet with answers
A voltmeter, an ammeter and a wattmeter connected to a single-phase inductive load read 120 V, 19.5 A and 1755 W. Find the reactive power Q taken by the load.
A single-phase motor takes 24 kW at a power factor of 0.9 lagging from a 230 V supply. Find the line current I.
An inductive load takes 13.5 A and 2174 W from a 230 V (rms) single-phase supply. Model it as a resistance R in series with a reactance X. Find R.
A 150 kVA single-phase transformer supplies a load of 92 kW at a power factor of 0.85 lagging. How much extra real power ΔP can be added as a resistive (unity power factor) load before the transformer reaches its kVA rating?
A single-phase load takes 20 kW at a power factor of 0.65 lagging from a 230 V, 50 Hz supply. A capacitor connected in parallel raises the power factor to 0.98. Find the capacitance C needed.
Answer key
- 1. S = 40.52 kVA
- 2. Q = 1548 var
- 3. I = 115.9 A
- 4. R = 11.93 Ω
- 5. ΔP = 46.74 kW
- 6. C = 1163 µF
Full step-by-step solutions: practise this topic on examproblems.com.