A load takes 22 kW of real power and 24.5 kvar of reactive power (lagging). Find the power factor cos φ.
AC power & power factor worksheet with answers
A single-phase load connected to a 400 V supply takes 16 kW and 6 kvar. Find the current I drawn from the supply.
An inductive load takes 14 A and 2737 W from a 230 V (rms) single-phase supply. Model it as a resistance R in series with a reactance X. Find X.
A single-phase motor takes 21 kW at a power factor of 0.6 lagging from a 240 V supply. Find the line current I.
A single-phase load takes 30 kW at a power factor of 0.65 lagging from a 230 V, 60 Hz supply. A capacitor connected in parallel raises the power factor to 0.92. Find the new line current Inew.
A single-phase load takes 30 kW at a power factor of 0.8 lagging from a 230 V, 60 Hz supply. A capacitor connected in parallel raises the power factor to 0.92. Find the capacitance C needed.
Answer key
- 1. cos φ = 0.6681
- 2. I = 42.72 A
- 3. X = 8.654 Ω
- 4. I = 145.8 A
- 5. Inew = 141.8 A
- 6. C = 487.4 µF