A single-phase load draws 14 A (rms) from a 120 V (rms) supply at a power factor of 0.85 lagging. Find the reactive power Q it takes.
AC power & power factor worksheet with answers
A voltmeter, an ammeter and a wattmeter connected to a single-phase inductive load read 230 V, 12 A and 1656 W. Find the reactive power Q taken by the load.
Two loads are connected in parallel to a 230 V single-phase supply: an 18 kW load at a power factor of 0.8 lagging and a 27 kW load at a power factor of 0.95 leading. Find the overall power factor cos φ seen by the supply.
An inductive load takes 13 A and 936 W from a 120 V (rms) single-phase supply. Model it as a resistance R in series with a reactance X. Find R.
A single-phase load takes 40 kW at a power factor of 0.7 lagging from a 400 V, 60 Hz supply. A capacitor connected in parallel raises the power factor to 0.9. Find the new line current Inew.
A single-phase load takes 23 kW at a power factor of 0.6 lagging from a 240 V, 60 Hz supply. A 150 µF capacitor is connected in parallel with the load. Find the new line current I.
Answer key
- 1. Q = 885 var
- 2. Q = 2208 var
- 3. cos φ = 0.9948
- 4. R = 5.538 Ω
- 5. Inew = 111.1 A
- 6. I = 149.1 A
Full step-by-step solutions: practise this topic on examproblems.com.