A single-phase load draws 11 A (rms) from a 230 V (rms) supply at a power factor of 0.85 lagging. Find the reactive power Q it takes.
AC power & power factor worksheet with answers
A single-phase load connected to a 240 V supply takes 9.5 kW and 5 kvar. Find the current I drawn from the supply.
A single-phase motor takes 3 kW at a power factor of 0.6 lagging from a 230 V supply. Find the reactive power Q it draws.
A single-phase motor takes 36 kW at a power factor of 0.7 lagging from a 240 V supply. Find the reactive power Q it draws.
A single-phase load takes 50 kW at a power factor of 0.65 lagging from a 230 V, 60 Hz supply. A capacitor connected in parallel raises the power factor to 0.95. Find the new line current Inew.
A single-phase load takes 22 kW at a power factor of 0.8 lagging from a 400 V, 60 Hz supply. A 220 µF capacitor is connected in parallel with the load. Find the new line current I.
Answer key
- 1. Q = 1333 var
- 2. I = 44.73 A
- 3. Q = 4 kvar
- 4. Q = 36.73 kvar
- 5. Inew = 228.8 A
- 6. I = 55.59 A
Full step-by-step solutions: practise this topic on examproblems.com.