A single-phase load draws 10 A (rms) from a 240 V (rms) supply at a power factor of 0.9 lagging. Find the reactive power Q it takes.
AC power & power factor worksheet with answers
A single-phase load draws 7 A (rms) from a 240 V (rms) supply at a power factor of 0.95 lagging. Find the reactive power Q it takes.
A single-phase motor takes 9 kW at a power factor of 0.75 lagging from a 400 V supply. Find the line current I.
A single-phase motor takes 29 kW at a power factor of 0.85 lagging from a 400 V supply. Find the line current I.
A 200 kVA single-phase transformer supplies a load of 88 kW at a power factor of 0.8 lagging. How much extra real power ΔP can be added as a resistive (unity power factor) load before the transformer reaches its kVA rating?
A single-phase load takes 25 kW at a power factor of 0.7 lagging from a 240 V, 50 Hz supply. A capacitor connected in parallel raises the power factor to 0.9. Find the new line current Inew.
Answer key
- 1. Q = 1046 var
- 2. Q = 524.6 var
- 3. I = 30 A
- 4. I = 85.29 A
- 5. ΔP = 100.8 kW
- 6. Inew = 115.7 A
Full step-by-step solutions: practise this topic on examproblems.com.