A single-phase load draws 15 A (rms) from a 400 V (rms) supply at a power factor of 0.7 lagging. Find the real power P it takes.
AC power & power factor worksheet with answers
A single-phase load draws 20 A (rms) from a 240 V (rms) supply at a power factor of 0.6 lagging. Find the reactive power Q it takes.
A load with impedance Z = 16 + j12 Ω is connected to a 120 V (rms) single-phase supply. Find the reactive power Q it absorbs.
A single-phase motor takes 24 kW at a power factor of 0.65 lagging from a 240 V supply. Find the line current I.
A 24 V (rms), 1000 Hz source has an internal impedance Zs = 25 + j30 Ω. The load impedance ZL can be chosen freely. Find the maximum real power Pmax that can be delivered to the load.
A single-phase load takes 30 kW at a power factor of 0.8 lagging from a 240 V, 50 Hz supply. A capacitor connected in parallel raises the power factor to 0.98. Find the capacitance C needed.
Answer key
- 1. P = 4200 W
- 2. Q = 3840 var
- 3. Q = 432 var
- 4. I = 153.8 A
- 5. Pmax = 5.76 W
- 6. C = 906.8 µF
Full step-by-step solutions: practise this topic on examproblems.com.