A single-phase load draws 11 A (rms) from a 400 V (rms) supply at a power factor of 0.7 lagging. Find the reactive power Q it takes.
AC power & power factor worksheet with answers
A single-phase load connected to a 230 V supply takes 19 kW and 21 kvar. Find the current I drawn from the supply.
A load with impedance Z = 20 + j15 Ω is connected to a 120 V (rms) single-phase supply. Find the real power P it absorbs.
A load with impedance Z = 24 + j7 Ω is connected to a 120 V (rms) single-phase supply. Find the real power P it absorbs.
A 200 kVA single-phase transformer supplies a load of 59 kW at a power factor of 0.75 lagging. How much extra real power ΔP can be added as a resistive (unity power factor) load before the transformer reaches its kVA rating?
A 230 V (rms), 50 Hz source has an internal impedance Zs = 50 + j5 Ω. The load impedance ZL can be chosen freely. Find the maximum real power Pmax that can be delivered to the load.
Answer key
- 1. Q = 3142 var
- 2. I = 123.1 A
- 3. P = 460.8 W
- 4. P = 553 W
- 5. ΔP = 134.1 kW
- 6. Pmax = 264.5 W
Full step-by-step solutions: practise this topic on examproblems.com.