A single-phase load connected to a 240 V supply takes 27.5 kW and 24 kvar. Find the current I drawn from the supply.
AC power & power factor worksheet with answers
A voltmeter, an ammeter and a wattmeter connected to a single-phase inductive load read 230 V, 14 A and 2576 W. Find the reactive power Q taken by the load.
A single-phase motor takes 11 kW at a power factor of 0.85 lagging from a 240 V supply. Find the line current I.
Two loads are connected in parallel to a 400 V single-phase supply: a 25 kW load at a power factor of 0.6 lagging and a 4 kW load at a power factor of 0.9 leading. Find the total current I drawn from the supply.
A single-phase load takes 19 kW at a power factor of 0.6 lagging from a 240 V, 50 Hz supply. A 220 µF capacitor is connected in parallel with the load. Find the new line current I.
A 100 V (rms), 60 Hz source has an internal impedance Zs = 50 + j3 Ω. The load impedance ZL can be chosen freely. Find the maximum real power Pmax that can be delivered to the load.
Answer key
- 1. I = 152.1 A
- 2. Q = 1932 var
- 3. I = 53.92 A
- 4. I = 106.9 A
- 5. I = 119.1 A
- 6. Pmax = 50 W