A single-phase load draws 7 A (rms) from a 240 V (rms) supply at a power factor of 0.95 lagging. Find the real power P it takes.
AC power & power factor worksheet with answers
A single-phase load draws 15 A (rms) from a 230 V (rms) supply at a power factor of 0.7 lagging. Find the reactive power Q it takes.
A load with impedance Z = 20 + j15 Ω is connected to a 230 V (rms) single-phase supply. Find the apparent power S.
Two loads are connected in parallel to a 230 V single-phase supply: a 5 kW load at a power factor of 0.6 lagging and a 29 kW heater (unity power factor). Find the total current I drawn from the supply.
A single-phase load takes 40 kW at a power factor of 0.6 lagging from a 240 V, 60 Hz supply. A capacitor connected in parallel raises the power factor to 0.9. Find the new line current Inew.
A single-phase load takes 26 kW at a power factor of 0.7 lagging from a 230 V, 60 Hz supply. A 330 µF capacitor is connected in parallel with the load. Find the new line current I.
Answer key
- 1. P = 1596 W
- 2. Q = 2464 var
- 3. S = 2116 VA
- 4. I = 150.6 A
- 5. Inew = 185.2 A
- 6. I = 142.5 A
Full step-by-step solutions: practise this topic on examproblems.com.