A single-phase load connected to a 230 V supply takes 17.5 kW and 6 kvar. Find the current I drawn from the supply.
AC power & power factor worksheet with answers
A single-phase load draws 16 A (rms) from a 120 V (rms) supply at a power factor of 0.95 lagging. Find the reactive power Q it takes.
A single-phase motor takes 40 kW at a power factor of 0.8 lagging from a 230 V supply. Find the line current I.
A single-phase motor takes 33 kW at a power factor of 0.75 lagging from a 230 V supply. Find the reactive power Q it draws.
A single-phase load takes 22 kW at a power factor of 0.7 lagging from a 230 V, 50 Hz supply. A 330 µF capacitor is connected in parallel with the load. Find the new line current I.
A single-phase load takes 8 kW at a power factor of 0.8 lagging from a 400 V, 50 Hz supply. A 47 µF capacitor is connected in parallel with the load. Find the new line current I.
Answer key
- 1. I = 80.43 A
- 2. Q = 599.5 var
- 3. I = 217.4 A
- 4. Q = 29.1 kvar
- 5. I = 120.8 A
- 6. I = 21.97 A
Full step-by-step solutions: practise this topic on examproblems.com.