A single-phase load draws 7 A (rms) from a 120 V (rms) supply at a power factor of 0.65 lagging. Find the real power P it takes.
AC power & power factor worksheet with answers
A single-phase load draws 3 A (rms) from a 120 V (rms) supply at a power factor of 0.8 lagging. Find the reactive power Q it takes.
A single-phase motor takes 3 kW at a power factor of 0.8 lagging from a 230 V supply. Find the line current I.
A single-phase motor takes 38 kW at a power factor of 0.65 lagging from a 240 V supply. Find the line current I.
A single-phase load takes 15 kW at a power factor of 0.65 lagging from a 400 V, 50 Hz supply. A capacitor connected in parallel raises the power factor to 0.9. Find the new line current Inew.
A 50 kVA single-phase transformer supplies a load of 25 kW at a power factor of 0.8 lagging. How much extra real power ΔP can be added as a resistive (unity power factor) load before the transformer reaches its kVA rating?
Answer key
- 1. P = 546 W
- 2. Q = 216 var
- 3. I = 16.3 A
- 4. I = 243.6 A
- 5. Inew = 41.67 A
- 6. ΔP = 21.35 kW
Full step-by-step solutions: practise this topic on examproblems.com.