In a counter-flow heat exchanger the hot fluid cools from 155 to 120 °C while the cold fluid heats from 15 to 40 °C. Find the log-mean temperature difference ΔTlm.
Heat exchangers (LMTD) worksheet with answers
In a counter-flow heat exchanger the hot fluid cools from 95 to 55 °C while the cold fluid heats from 30 to 40 °C. Find the log-mean temperature difference ΔTlm.
A shell-and-tube heat exchanger (one shell pass, two tube passes) must transfer 210 kW. The hot fluid cools from 100 to 35 °C and the cold fluid heats from 20 to 80 °C. The LMTD correction factor for this arrangement is F = 0.95, and U = 1000 W/(m²·K). Find the heat transfer area A needed.
A parallel-flow heat exchanger transfers 160 kW. The hot fluid cools from 105 to 60 °C and the cold fluid heats from 25 to 45 °C. The overall heat transfer coefficient is 800 W/(m²·K). Find the heat transfer area A needed.
In a counter-flow heat exchanger both streams have the same heat capacity rate, ṁ·cp = 4 kW/K. The hot stream enters at 110 °C and the cold stream at 20 °C. The exchanger has A = 1.5 m² and U = 800 W/(m²·K). Find the hot outlet temperature Th,out.
Hot oil (0.5 kg/s, cp = 2.1 kJ/(kg·K)) cools from 140 to 120 °C in a counter-flow exchanger. It heats 2 kg/s of water (cp = 4.18 kJ/(kg·K)) that enters at 30 °C. With U = 200 W/(m²·K), find the heat transfer area A needed.
Answer key
- 1. ΔTlm = 109.9 K
- 2. ΔTlm = 38.05 K
- 3. A = 12.72 m²
- 4. A = 5.151 m²
- 5. Th,out = 89.23 °C
- 6. A = 1.066 m²
Full step-by-step solutions: practise this topic on examproblems.com.