Hot oil (0.5 kg/s, cp = 2.3 kJ/(kg·K)) cools from 175 to 85 °C in a counter-flow exchanger. It heats 1 kg/s of water (cp = 4.18 kJ/(kg·K)) that enters at 25 °C. No heat is lost to the surroundings. Find the water outlet temperature Tc,out.
Heat exchangers (LMTD) worksheet with answers
In a counter-flow heat exchanger the hot fluid cools from 120 to 65 °C while the cold fluid heats from 15 to 75 °C. Find the log-mean temperature difference ΔTlm.
In a condenser, steam condenses at a constant 105 °C on the outside of the tubes. Cooling water (1 kg/s, cp = 4.18 kJ/(kg·K)) flows through the tubes and heats from 10 to 95 °C. The overall heat transfer coefficient is 3000 W/(m²·K). Find the heat transfer area A needed.
A counter-flow heat exchanger transfers 150 kW. The hot fluid cools from 180 to 55 °C and the cold fluid heats from 20 to 125 °C. The overall heat transfer coefficient is 1000 W/(m²·K). Find the heat transfer area A needed.
Hot oil (2 kg/s, cp = 2.3 kJ/(kg·K)) cools from 160 to 120 °C in a counter-flow exchanger. It heats 1 kg/s of water (cp = 4.18 kJ/(kg·K)) that enters at 25 °C. With U = 200 W/(m²·K), find the heat transfer area A needed.
Hot oil (1 kg/s, cp = 2.3 kJ/(kg·K)) cools from 85 to 45 °C in a counter-flow exchanger. It heats 1.5 kg/s of water (cp = 4.18 kJ/(kg·K)) that enters at 25 °C. With U = 200 W/(m²·K), find the heat transfer area A needed.
Answer key
- 1. Tc,out = 49.76 °C
- 2. ΔTlm = 47.46 K
- 3. A = 3.137 m²
- 4. A = 3.39 m²
- 5. A = 9.895 m²
- 6. A = 14.86 m²