In a parallel-flow heat exchanger the hot fluid cools from 140 to 115 °C while the cold fluid heats from 15 to 65 °C. Find the log-mean temperature difference ΔTlm.
Heat exchangers (LMTD) worksheet with answers
In a heat exchanger 1.5 kg/s of water (cp = 4.18 kJ/(kg·K)) is cooled from 120 to 75 °C. Find the heat transfer rate Q̇.
A counter-flow heat exchanger transfers 30 kW. The hot fluid cools from 145 to 115 °C and the cold fluid heats from 15 to 125 °C. The overall heat transfer coefficient is 300 W/(m²·K). Find the heat transfer area A needed.
A counter-flow heat exchanger transfers 490 kW. The hot fluid cools from 115 to 45 °C and the cold fluid heats from 25 to 105 °C. The overall heat transfer coefficient is 200 W/(m²·K). Find the heat transfer area A needed.
In a counter-flow heat exchanger both streams have the same heat capacity rate, ṁ·cp = 3 kW/K. The hot stream enters at 150 °C and the cold stream at 10 °C. The exchanger has A = 3 m² and U = 800 W/(m²·K). Find the hot outlet temperature Th,out.
Hot oil (1 kg/s, cp = 2.5 kJ/(kg·K)) cools from 165 to 140 °C in a counter-flow exchanger. It heats 0.5 kg/s of water (cp = 4.18 kJ/(kg·K)) that enters at 25 °C. With U = 200 W/(m²·K), find the heat transfer area A needed.
Answer key
- 1. ΔTlm = 81.85 K
- 2. Q̇ = 282.1 kW
- 3. A = 2.012 m²
- 4. A = 169.8 m²
- 5. Th,out = 87.78 °C
- 6. A = 2.777 m²
Full step-by-step solutions: practise this topic on examproblems.com.