In a heat exchanger 1 kg/s of light oil (cp = 2.1 kJ/(kg·K)) is cooled from 60 to 35 °C. Find the heat transfer rate Q̇.
Heat exchangers (LMTD) worksheet with answers
Hot oil (1.5 kg/s, cp = 2.1 kJ/(kg·K)) cools from 115 to 65 °C in a counter-flow exchanger. It heats 1 kg/s of water (cp = 4.18 kJ/(kg·K)) that enters at 30 °C. No heat is lost to the surroundings. Find the water outlet temperature Tc,out.
A counter-flow heat exchanger transfers 480 kW. The hot fluid cools from 115 to 55 °C and the cold fluid heats from 30 to 60 °C. The overall heat transfer coefficient is 300 W/(m²·K). Find the heat transfer area A needed.
A counter-flow heat exchanger transfers 300 kW. The hot fluid cools from 90 to 35 °C and the cold fluid heats from 15 to 45 °C. The overall heat transfer coefficient is 200 W/(m²·K). Find the heat transfer area A needed.
Steam condenses at a constant 140 °C on the outside of the tubes of a condenser with a heat transfer area of 2 m² and U = 2000 W/(m²·K). Cooling water (1 kg/s, cp = 4.18 kJ/(kg·K)) enters the tubes at 15 °C. Find the water outlet temperature Tc,out.
In a counter-flow heat exchanger both streams have the same heat capacity rate, ṁ·cp = 0.5 kW/K. The hot stream enters at 105 °C and the cold stream at 30 °C. The exchanger has A = 0.5 m² and U = 500 W/(m²·K). Find the hot outlet temperature Th,out.
Answer key
- 1. Q̇ = 52.5 kW
- 2. Tc,out = 67.68 °C
- 3. A = 42.05 m²
- 4. A = 48.66 m²
- 5. Tc,out = 91.99 °C
- 6. Th,out = 80 °C
Full step-by-step solutions: practise this topic on examproblems.com.