In a parallel-flow heat exchanger the hot fluid cools from 140 to 85 °C while the cold fluid heats from 15 to 45 °C. Find the log-mean temperature difference ΔTlm.
Heat exchangers (LMTD) worksheet with answers
In a counter-flow heat exchanger the hot fluid cools from 170 to 55 °C while the cold fluid heats from 10 to 115 °C. Find the log-mean temperature difference ΔTlm.
In a condenser, steam condenses at a constant 100 °C on the outside of the tubes. Cooling water (5 kg/s, cp = 4.18 kJ/(kg·K)) flows through the tubes and heats from 20 to 60 °C. The overall heat transfer coefficient is 3500 W/(m²·K). Find the heat transfer area A needed.
A counter-flow heat exchanger transfers 110 kW. The hot fluid cools from 105 to 25 °C and the cold fluid heats from 10 to 55 °C. The overall heat transfer coefficient is 200 W/(m²·K). Find the heat transfer area A needed.
In a counter-flow double-pipe heat exchanger, hot oil (0.3 kg/s, cp = 2.1 kJ/(kg·K)) flows in the inner tube and cools from 120 to 65 °C. Water (0.2 kg/s, cp = 4.18 kJ/(kg·K)) in the annulus enters at 10 °C. The inner tube has a diameter of 50 mm, and U = 250 W/(m²·K) is based on this diameter. Find the tube length L needed.
In a counter-flow heat exchanger both streams have the same heat capacity rate, ṁ·cp = 2 kW/K. The hot stream enters at 135 °C and the cold stream at 25 °C. The exchanger has A = 6 m² and U = 200 W/(m²·K). Find the hot outlet temperature Th,out.
Answer key
- 1. ΔTlm = 74.6 K
- 2. ΔTlm = 49.83 K
- 3. A = 4.139 m²
- 4. A = 18.92 m²
- 5. L = 14.34 m
- 6. Th,out = 93.75 °C
Full step-by-step solutions: practise this topic on examproblems.com.