Hot oil (1 kg/s, cp = 2.3 kJ/(kg·K)) cools from 110 to 70 °C in a counter-flow exchanger. It heats 0.5 kg/s of water (cp = 4.18 kJ/(kg·K)) that enters at 15 °C. No heat is lost to the surroundings. Find the water outlet temperature Tc,out.
Heat exchangers (LMTD) worksheet with answers
In a counter-flow heat exchanger the hot fluid cools from 90 to 45 °C while the cold fluid heats from 20 to 55 °C. Find the log-mean temperature difference ΔTlm.
A counter-flow heat exchanger transfers 90 kW. The hot fluid cools from 170 to 145 °C and the cold fluid heats from 10 to 110 °C. The overall heat transfer coefficient is 500 W/(m²·K). Find the heat transfer area A needed.
A shell-and-tube heat exchanger (one shell pass, two tube passes) must transfer 670 kW. The hot fluid cools from 90 to 75 °C and the cold fluid heats from 20 to 70 °C. The LMTD correction factor for this arrangement is F = 0.9, and U = 200 W/(m²·K). Find the heat transfer area A needed.
Hot oil (0.5 kg/s, cp = 2.5 kJ/(kg·K)) cools from 120 to 30 °C in a counter-flow exchanger. It heats 2 kg/s of water (cp = 4.18 kJ/(kg·K)) that enters at 10 °C. With U = 1500 W/(m²·K), find the heat transfer area A needed.
In a counter-flow double-pipe heat exchanger, hot oil (0.5 kg/s, cp = 2.1 kJ/(kg·K)) flows in the inner tube and cools from 160 to 90 °C. Water (0.5 kg/s, cp = 4.18 kJ/(kg·K)) in the annulus enters at 10 °C. The inner tube has a diameter of 20 mm, and U = 200 W/(m²·K) is based on this diameter. Find the tube length L needed.
Answer key
- 1. Tc,out = 59.02 °C
- 2. ΔTlm = 29.72 K
- 3. A = 1.946 m²
- 4. A = 107.6 m²
- 5. A = 1.543 m²
- 6. L = 60.69 m
Full step-by-step solutions: practise this topic on examproblems.com.