In a heat exchanger 2.5 kg/s of water (cp = 4.18 kJ/(kg·K)) is cooled from 75 to 60 °C. Find the heat transfer rate Q̇.
Heat exchangers (LMTD) worksheet with answers
In a counter-flow heat exchanger the hot fluid cools from 100 to 65 °C while the cold fluid heats from 15 to 60 °C. Find the log-mean temperature difference ΔTlm.
A counter-flow heat exchanger transfers 480 kW. The hot fluid cools from 135 to 45 °C and the cold fluid heats from 25 to 120 °C. The overall heat transfer coefficient is 200 W/(m²·K). Find the heat transfer area A needed.
A counter-flow heat exchanger transfers 70 kW. The hot fluid cools from 160 to 140 °C and the cold fluid heats from 15 to 45 °C. The overall heat transfer coefficient is 200 W/(m²·K). Find the heat transfer area A needed.
In a counter-flow double-pipe heat exchanger, hot oil (0.8 kg/s, cp = 2.3 kJ/(kg·K)) flows in the inner tube and cools from 90 to 60 °C. Water (0.5 kg/s, cp = 4.18 kJ/(kg·K)) in the annulus enters at 10 °C. The inner tube has a diameter of 40 mm, and U = 500 W/(m²·K) is based on this diameter. Find the tube length L needed.
Steam condenses at a constant 140 °C on the outside of the tubes of a condenser with a heat transfer area of 3 m² and U = 2000 W/(m²·K). Cooling water (1.5 kg/s, cp = 4.18 kJ/(kg·K)) enters the tubes at 20 °C. Find the water outlet temperature Tc,out.
Answer key
- 1. Q̇ = 156.8 kW
- 2. ΔTlm = 44.81 K
- 3. A = 138.1 m²
- 4. A = 2.918 m²
- 5. L = 16.97 m
- 6. Tc,out = 93.91 °C
Full step-by-step solutions: practise this topic on examproblems.com.