Hot oil (1 kg/s, cp = 2.5 kJ/(kg·K)) cools from 130 to 70 °C in a counter-flow exchanger. It heats 2 kg/s of water (cp = 4.18 kJ/(kg·K)) that enters at 25 °C. No heat is lost to the surroundings. Find the water outlet temperature Tc,out.
Heat exchangers (LMTD) worksheet with answers
In a counter-flow heat exchanger the hot fluid cools from 120 to 35 °C while the cold fluid heats from 20 to 35 °C. Find the log-mean temperature difference ΔTlm.
A counter-flow heat exchanger transfers 290 kW. The hot fluid cools from 140 to 125 °C and the cold fluid heats from 15 to 125 °C. The overall heat transfer coefficient is 200 W/(m²·K). Find the heat transfer area A needed.
A counter-flow heat exchanger transfers 390 kW. The hot fluid cools from 115 to 85 °C and the cold fluid heats from 15 to 100 °C. The overall heat transfer coefficient is 1000 W/(m²·K). Find the heat transfer area A needed.
In a counter-flow double-pipe heat exchanger, hot oil (0.5 kg/s, cp = 2.1 kJ/(kg·K)) flows in the inner tube and cools from 160 to 130 °C. Water (1.5 kg/s, cp = 4.18 kJ/(kg·K)) in the annulus enters at 15 °C. The inner tube has a diameter of 25 mm, and U = 250 W/(m²·K) is based on this diameter. Find the tube length L needed.
Hot oil (2 kg/s, cp = 2.3 kJ/(kg·K)) cools from 135 to 90 °C in a counter-flow exchanger. It heats 1.5 kg/s of water (cp = 4.18 kJ/(kg·K)) that enters at 30 °C. With U = 200 W/(m²·K), find the heat transfer area A needed.
Answer key
- 1. Tc,out = 42.94 °C
- 2. ΔTlm = 40.36 K
- 3. A = 30.41 m²
- 4. A = 10.92 m²
- 5. L = 12.62 m
- 6. A = 15.73 m²