A counter-flow heat exchanger has a heat transfer area of 6 m² and an overall heat transfer coefficient of 800 W/(m²·K). The hot fluid cools from 140 to 60 °C and the cold fluid heats from 15 to 125 °C. Find the heat transfer rate Q̇.
Heat exchangers (LMTD) worksheet with answers
Hot oil (1 kg/s, cp = 2.3 kJ/(kg·K)) cools from 140 to 80 °C in a counter-flow exchanger. It heats 1 kg/s of water (cp = 4.18 kJ/(kg·K)) that enters at 25 °C. No heat is lost to the surroundings. Find the water outlet temperature Tc,out.
In a condenser, steam condenses at a constant 100 °C on the outside of the tubes. Cooling water (3 kg/s, cp = 4.18 kJ/(kg·K)) flows through the tubes and heats from 15 to 40 °C. The overall heat transfer coefficient is 2500 W/(m²·K). Find the heat transfer area A needed.
In a condenser, steam condenses at a constant 140 °C on the outside of the tubes. Cooling water (2 kg/s, cp = 4.18 kJ/(kg·K)) flows through the tubes and heats from 20 to 105 °C. The overall heat transfer coefficient is 3500 W/(m²·K). Find the heat transfer area A needed.
In a counter-flow heat exchanger both streams have the same heat capacity rate, ṁ·cp = 1.5 kW/K. The hot stream enters at 120 °C and the cold stream at 30 °C. The exchanger has A = 4 m² and U = 500 W/(m²·K). Find the hot outlet temperature Th,out.
Hot oil (2 kg/s, cp = 2.5 kJ/(kg·K)) cools from 150 to 65 °C in a counter-flow exchanger. It heats 1 kg/s of water (cp = 4.18 kJ/(kg·K)) that enters at 15 °C. With U = 300 W/(m²·K), find the heat transfer area A needed.
Answer key
- 1. Q̇ = 131.1 kW
- 2. Tc,out = 58.01 °C
- 3. A = 1.747 m²
- 4. A = 2.943 m²
- 5. Th,out = 68.57 °C
- 6. A = 34.47 m²
Full step-by-step solutions: practise this topic on examproblems.com.