In a counter-flow heat exchanger the hot fluid cools from 130 to 100 °C while the cold fluid heats from 20 to 100 °C. Find the log-mean temperature difference ΔTlm.
Heat exchangers (LMTD) worksheet with answers
In a counter-flow heat exchanger the hot fluid cools from 90 to 40 °C while the cold fluid heats from 15 to 35 °C. Find the log-mean temperature difference ΔTlm.
A shell-and-tube heat exchanger (one shell pass, two tube passes) must transfer 500 kW. The hot fluid cools from 155 to 40 °C and the cold fluid heats from 20 to 35 °C. The LMTD correction factor for this arrangement is F = 0.95, and U = 1000 W/(m²·K). Find the heat transfer area A needed.
A counter-flow heat exchanger transfers 380 kW. The hot fluid cools from 125 to 50 °C and the cold fluid heats from 15 to 25 °C. The overall heat transfer coefficient is 500 W/(m²·K). Find the heat transfer area A needed.
In a counter-flow double-pipe heat exchanger, hot oil (0.3 kg/s, cp = 2.1 kJ/(kg·K)) flows in the inner tube and cools from 115 to 80 °C. Water (0.5 kg/s, cp = 4.18 kJ/(kg·K)) in the annulus enters at 20 °C. The inner tube has a diameter of 25 mm, and U = 250 W/(m²·K) is based on this diameter. Find the tube length L needed.
Steam condenses at a constant 100 °C on the outside of the tubes of a condenser with a heat transfer area of 8 m² and U = 1000 W/(m²·K). Cooling water (3 kg/s, cp = 4.18 kJ/(kg·K)) enters the tubes at 30 °C. Find the water outlet temperature Tc,out.
Answer key
- 1. ΔTlm = 50.98 K
- 2. ΔTlm = 38.05 K
- 3. A = 9.43 m²
- 4. A = 12.27 m²
- 5. L = 15.7 m
- 6. Tc,out = 63.01 °C