Hot oil (1.5 kg/s, cp = 2.1 kJ/(kg·K)) cools from 115 to 85 °C in a counter-flow exchanger. It heats 1 kg/s of water (cp = 4.18 kJ/(kg·K)) that enters at 15 °C. No heat is lost to the surroundings. Find the water outlet temperature Tc,out.
Heat exchangers (LMTD) worksheet with answers
In a parallel-flow heat exchanger the hot fluid cools from 105 to 90 °C while the cold fluid heats from 10 to 20 °C. Find the log-mean temperature difference ΔTlm.
In a condenser, steam condenses at a constant 105 °C on the outside of the tubes. Cooling water (0.5 kg/s, cp = 4.18 kJ/(kg·K)) flows through the tubes and heats from 10 to 55 °C. The overall heat transfer coefficient is 3000 W/(m²·K). Find the heat transfer area A needed.
A shell-and-tube heat exchanger (one shell pass, two tube passes) must transfer 230 kW. The hot fluid cools from 140 to 105 °C and the cold fluid heats from 25 to 130 °C. The LMTD correction factor for this arrangement is F = 0.92, and U = 500 W/(m²·K). Find the heat transfer area A needed.
Steam condenses at a constant 130 °C on the outside of the tubes of a condenser with a heat transfer area of 2.5 m² and U = 3000 W/(m²·K). Cooling water (1 kg/s, cp = 4.18 kJ/(kg·K)) enters the tubes at 30 °C. Find the water outlet temperature Tc,out.
In a counter-flow heat exchanger both streams have the same heat capacity rate, ṁ·cp = 0.5 kW/K. The hot stream enters at 150 °C and the cold stream at 15 °C. The exchanger has A = 1.5 m² and U = 200 W/(m²·K). Find the hot outlet temperature Th,out.
Answer key
- 1. Tc,out = 37.61 °C
- 2. ΔTlm = 81.86 K
- 3. A = 0.4472 m²
- 4. A = 14.85 m²
- 5. Tc,out = 113.4 °C
- 6. Th,out = 99.38 °C
Full step-by-step solutions: practise this topic on examproblems.com.