In a counter-flow heat exchanger the hot fluid cools from 100 to 65 °C while the cold fluid heats from 10 to 75 °C. Find the log-mean temperature difference ΔTlm.
Heat exchangers (LMTD) worksheet with answers
In a counter-flow heat exchanger the hot fluid cools from 95 to 30 °C while the cold fluid heats from 15 to 45 °C. Find the log-mean temperature difference ΔTlm.
A parallel-flow heat exchanger transfers 220 kW. The hot fluid cools from 175 to 135 °C and the cold fluid heats from 25 to 65 °C. The overall heat transfer coefficient is 1000 W/(m²·K). Find the heat transfer area A needed.
A shell-and-tube heat exchanger (one shell pass, two tube passes) must transfer 210 kW. The hot fluid cools from 90 to 45 °C and the cold fluid heats from 30 to 60 °C. The LMTD correction factor for this arrangement is F = 0.85, and U = 300 W/(m²·K). Find the heat transfer area A needed.
In a counter-flow double-pipe heat exchanger, hot oil (0.3 kg/s, cp = 2.5 kJ/(kg·K)) flows in the inner tube and cools from 160 to 100 °C. Water (1 kg/s, cp = 4.18 kJ/(kg·K)) in the annulus enters at 20 °C. The inner tube has a diameter of 20 mm, and U = 400 W/(m²·K) is based on this diameter. Find the tube length L needed.
In a counter-flow double-pipe heat exchanger, hot oil (0.3 kg/s, cp = 2.5 kJ/(kg·K)) flows in the inner tube and cools from 110 to 75 °C. Water (0.2 kg/s, cp = 4.18 kJ/(kg·K)) in the annulus enters at 15 °C. The inner tube has a diameter of 40 mm, and U = 500 W/(m²·K) is based on this diameter. Find the tube length L needed.
Answer key
- 1. ΔTlm = 38.05 K
- 2. ΔTlm = 29.07 K
- 3. A = 2.096 m²
- 4. A = 38.06 m²
- 5. L = 17.44 m
- 6. L = 6.762 m
Full step-by-step solutions: practise this topic on examproblems.com.