Hot oil (2 kg/s, cp = 2.3 kJ/(kg·K)) cools from 130 to 60 °C in a counter-flow exchanger. It heats 1.5 kg/s of water (cp = 4.18 kJ/(kg·K)) that enters at 15 °C. No heat is lost to the surroundings. Find the water outlet temperature Tc,out.
Heat exchangers (LMTD) worksheet with answers
In a parallel-flow heat exchanger the hot fluid cools from 90 to 60 °C while the cold fluid heats from 20 to 30 °C. Find the log-mean temperature difference ΔTlm.
A shell-and-tube heat exchanger (one shell pass, two tube passes) must transfer 260 kW. The hot fluid cools from 180 to 100 °C and the cold fluid heats from 20 to 30 °C. The LMTD correction factor for this arrangement is F = 0.9, and U = 200 W/(m²·K). Find the heat transfer area A needed.
A counter-flow heat exchanger transfers 400 kW. Its heat transfer area is 3 m². The hot fluid cools from 170 to 120 °C and the cold fluid heats from 25 to 145 °C. Find the overall heat transfer coefficient U.
In a counter-flow double-pipe heat exchanger, hot oil (0.3 kg/s, cp = 2.5 kJ/(kg·K)) flows in the inner tube and cools from 100 to 65 °C. Water (1.5 kg/s, cp = 4.18 kJ/(kg·K)) in the annulus enters at 15 °C. The inner tube has a diameter of 32 mm, and U = 500 W/(m²·K) is based on this diameter. Find the tube length L needed.
In a counter-flow double-pipe heat exchanger, hot oil (0.3 kg/s, cp = 2.1 kJ/(kg·K)) flows in the inner tube and cools from 100 to 60 °C. Water (0.3 kg/s, cp = 4.18 kJ/(kg·K)) in the annulus enters at 10 °C. The inner tube has a diameter of 32 mm, and U = 150 W/(m²·K) is based on this diameter. Find the tube length L needed.
Answer key
- 1. Tc,out = 66.36 °C
- 2. ΔTlm = 47.21 K
- 3. A = 12.97 m²
- 4. U = 2543 W/(m²·K)
- 5. L = 8.137 m
- 6. L = 28.13 m