Hot oil (1 kg/s, cp = 2.3 kJ/(kg·K)) cools from 165 to 65 °C in a counter-flow exchanger. It heats 1 kg/s of water (cp = 4.18 kJ/(kg·K)) that enters at 10 °C. No heat is lost to the surroundings. Find the water outlet temperature Tc,out.
Heat exchangers (LMTD) worksheet with answers
In a counter-flow heat exchanger the hot fluid cools from 100 to 60 °C while the cold fluid heats from 25 to 50 °C. Find the log-mean temperature difference ΔTlm.
A parallel-flow heat exchanger transfers 40 kW. Its heat transfer area is 2.5 m². The hot fluid cools from 110 to 60 °C and the cold fluid heats from 10 to 45 °C. Find the overall heat transfer coefficient U.
A counter-flow heat exchanger transfers 140 kW. The hot fluid cools from 130 to 95 °C and the cold fluid heats from 30 to 115 °C. The overall heat transfer coefficient is 800 W/(m²·K). Find the heat transfer area A needed.
In a counter-flow heat exchanger both streams have the same heat capacity rate, ṁ·cp = 2 kW/K. The hot stream enters at 170 °C and the cold stream at 25 °C. The exchanger has A = 3 m² and U = 500 W/(m²·K). Find the hot outlet temperature Th,out.
Hot oil (1.5 kg/s, cp = 2.5 kJ/(kg·K)) cools from 105 to 75 °C in a counter-flow exchanger. It heats 2 kg/s of water (cp = 4.18 kJ/(kg·K)) that enters at 25 °C. With U = 1000 W/(m²·K), find the heat transfer area A needed.
Answer key
- 1. Tc,out = 65.02 °C
- 2. ΔTlm = 42.06 K
- 3. U = 357.1 W/(m²·K)
- 4. A = 5.132 m²
- 5. Th,out = 107.9 °C
- 6. A = 1.944 m²