Hot oil (0.5 kg/s, cp = 2.1 kJ/(kg·K)) cools from 155 to 125 °C in a counter-flow exchanger. It heats 1 kg/s of water (cp = 4.18 kJ/(kg·K)) that enters at 30 °C. No heat is lost to the surroundings. Find the water outlet temperature Tc,out.
Heat exchangers (LMTD) worksheet with answers
In a counter-flow heat exchanger the hot fluid cools from 95 to 75 °C while the cold fluid heats from 15 to 45 °C. Find the log-mean temperature difference ΔTlm.
In a condenser, steam condenses at a constant 110 °C on the outside of the tubes. Cooling water (1 kg/s, cp = 4.18 kJ/(kg·K)) flows through the tubes and heats from 25 to 65 °C. The overall heat transfer coefficient is 2000 W/(m²·K). Find the heat transfer area A needed.
A parallel-flow heat exchanger transfers 350 kW. Its heat transfer area is 4 m². The hot fluid cools from 110 to 75 °C and the cold fluid heats from 15 to 40 °C. Find the overall heat transfer coefficient U.
In a counter-flow heat exchanger both streams have the same heat capacity rate, ṁ·cp = 0.5 kW/K. The hot stream enters at 165 °C and the cold stream at 10 °C. The exchanger has A = 2 m² and U = 800 W/(m²·K). Find the hot outlet temperature Th,out.
Hot oil (1 kg/s, cp = 2.1 kJ/(kg·K)) cools from 165 to 95 °C in a counter-flow exchanger. It heats 1 kg/s of water (cp = 4.18 kJ/(kg·K)) that enters at 30 °C. With U = 800 W/(m²·K), find the heat transfer area A needed.
Answer key
- 1. Tc,out = 37.54 °C
- 2. ΔTlm = 54.85 K
- 3. A = 1.329 m²
- 4. U = 1456 W/(m²·K)
- 5. Th,out = 46.9 °C
- 6. A = 2.264 m²