A counter-flow heat exchanger has a heat transfer area of 2.5 m² and an overall heat transfer coefficient of 800 W/(m²·K). The hot fluid cools from 170 to 50 °C and the cold fluid heats from 30 to 105 °C. Find the heat transfer rate Q̇.
Heat exchangers (LMTD) worksheet with answers
In a parallel-flow heat exchanger the hot fluid cools from 95 to 30 °C while the cold fluid heats from 10 to 25 °C. Find the log-mean temperature difference ΔTlm.
A counter-flow heat exchanger transfers 490 kW. The hot fluid cools from 155 to 45 °C and the cold fluid heats from 10 to 25 °C. The overall heat transfer coefficient is 300 W/(m²·K). Find the heat transfer area A needed.
A shell-and-tube heat exchanger (one shell pass, two tube passes) must transfer 50 kW. The hot fluid cools from 95 to 60 °C and the cold fluid heats from 25 to 65 °C. The LMTD correction factor for this arrangement is F = 0.88, and U = 500 W/(m²·K). Find the heat transfer area A needed.
In a counter-flow heat exchanger both streams have the same heat capacity rate, ṁ·cp = 1.5 kW/K. The hot stream enters at 155 °C and the cold stream at 10 °C. The exchanger has A = 2 m² and U = 300 W/(m²·K). Find the hot outlet temperature Th,out.
In a counter-flow heat exchanger both streams have the same heat capacity rate, ṁ·cp = 1 kW/K. The hot stream enters at 90 °C and the cold stream at 10 °C. The exchanger has A = 2 m² and U = 200 W/(m²·K). Find the hot outlet temperature Th,out.
Answer key
- 1. Q̇ = 76.36 kW
- 2. ΔTlm = 28.24 K
- 3. A = 22.56 m²
- 4. A = 3.503 m²
- 5. Th,out = 113.6 °C
- 6. Th,out = 67.14 °C