In a counter-flow heat exchanger the hot fluid cools from 145 to 45 °C while the cold fluid heats from 10 to 80 °C. Find the log-mean temperature difference ΔTlm.
Heat exchangers (LMTD) worksheet with answers
Hot oil (0.5 kg/s, cp = 2.1 kJ/(kg·K)) cools from 110 to 75 °C in a counter-flow exchanger. It heats 2 kg/s of water (cp = 4.18 kJ/(kg·K)) that enters at 30 °C. No heat is lost to the surroundings. Find the water outlet temperature Tc,out.
A counter-flow heat exchanger transfers 240 kW. The hot fluid cools from 110 to 40 °C and the cold fluid heats from 25 to 90 °C. The overall heat transfer coefficient is 500 W/(m²·K). Find the heat transfer area A needed.
In a condenser, steam condenses at a constant 140 °C on the outside of the tubes. Cooling water (0.5 kg/s, cp = 4.18 kJ/(kg·K)) flows through the tubes and heats from 10 to 80 °C. The overall heat transfer coefficient is 1500 W/(m²·K). Find the heat transfer area A needed.
Hot oil (1.5 kg/s, cp = 2.1 kJ/(kg·K)) cools from 85 to 60 °C in a counter-flow exchanger. It heats 3 kg/s of water (cp = 4.18 kJ/(kg·K)) that enters at 25 °C. With U = 1500 W/(m²·K), find the heat transfer area A needed.
In a parallel-flow double-pipe heat exchanger, hot oil (0.2 kg/s, cp = 2.1 kJ/(kg·K)) flows in the inner tube and cools from 155 to 95 °C. Water (1 kg/s, cp = 4.18 kJ/(kg·K)) in the annulus enters at 10 °C. The inner tube has a diameter of 32 mm, and U = 300 W/(m²·K) is based on this diameter. Find the tube length L needed.
Answer key
- 1. ΔTlm = 48.46 K
- 2. Tc,out = 34.4 °C
- 3. A = 27.62 m²
- 4. A = 1.077 m²
- 5. A = 1.202 m²
- 6. L = 7.69 m
Full step-by-step solutions: practise this topic on examproblems.com.