Hot oil (1 kg/s, cp = 2.3 kJ/(kg·K)) cools from 165 to 135 °C in a counter-flow exchanger. It heats 2 kg/s of water (cp = 4.18 kJ/(kg·K)) that enters at 15 °C. No heat is lost to the surroundings. Find the water outlet temperature Tc,out.
Heat exchangers (LMTD) worksheet with answers
In a heat exchanger 3 kg/s of ethanol (cp = 2.44 kJ/(kg·K)) is cooled from 65 to 35 °C. Find the heat transfer rate Q̇.
In a condenser, steam condenses at a constant 130 °C on the outside of the tubes. Cooling water (4 kg/s, cp = 4.18 kJ/(kg·K)) flows through the tubes and heats from 25 to 110 °C. The overall heat transfer coefficient is 1500 W/(m²·K). Find the heat transfer area A needed.
A shell-and-tube heat exchanger (one shell pass, two tube passes) must transfer 690 kW. The hot fluid cools from 155 to 30 °C and the cold fluid heats from 10 to 105 °C. The LMTD correction factor for this arrangement is F = 0.85, and U = 1000 W/(m²·K). Find the heat transfer area A needed.
In a counter-flow heat exchanger both streams have the same heat capacity rate, ṁ·cp = 0.5 kW/K. The hot stream enters at 165 °C and the cold stream at 30 °C. The exchanger has A = 4 m² and U = 300 W/(m²·K). Find the hot outlet temperature Th,out.
Hot oil (1 kg/s, cp = 2.5 kJ/(kg·K)) cools from 175 to 80 °C in a counter-flow exchanger. It heats 1 kg/s of water (cp = 4.18 kJ/(kg·K)) that enters at 25 °C. With U = 500 W/(m²·K), find the heat transfer area A needed.
Answer key
- 1. Tc,out = 23.25 °C
- 2. Q̇ = 219.6 kW
- 3. A = 18.48 m²
- 4. A = 24.79 m²
- 5. Th,out = 69.71 °C
- 6. A = 6.559 m²