In a heat exchanger 1 kg/s of light oil (cp = 2.1 kJ/(kg·K)) is cooled from 110 to 65 °C. Find the heat transfer rate Q̇.
Heat exchangers (LMTD) worksheet with answers
A counter-flow heat exchanger has a heat transfer area of 6 m² and an overall heat transfer coefficient of 200 W/(m²·K). The hot fluid cools from 105 to 45 °C and the cold fluid heats from 20 to 95 °C. Find the heat transfer rate Q̇.
A counter-flow heat exchanger transfers 370 kW. The hot fluid cools from 85 to 65 °C and the cold fluid heats from 10 to 35 °C. The overall heat transfer coefficient is 500 W/(m²·K). Find the heat transfer area A needed.
A parallel-flow heat exchanger transfers 330 kW. The hot fluid cools from 170 to 95 °C and the cold fluid heats from 25 to 65 °C. The overall heat transfer coefficient is 300 W/(m²·K). Find the heat transfer area A needed.
Steam condenses at a constant 105 °C on the outside of the tubes of a condenser with a heat transfer area of 3 m² and U = 1000 W/(m²·K). Cooling water (0.5 kg/s, cp = 4.18 kJ/(kg·K)) enters the tubes at 30 °C. Find the water outlet temperature Tc,out.
Hot oil (0.5 kg/s, cp = 2.1 kJ/(kg·K)) cools from 80 to 40 °C in a counter-flow exchanger. It heats 1 kg/s of water (cp = 4.18 kJ/(kg·K)) that enters at 15 °C. With U = 500 W/(m²·K), find the heat transfer area A needed.
Answer key
- 1. Q̇ = 94.5 kW
- 2. Q̇ = 19.64 kW
- 3. A = 14.11 m²
- 4. A = 15.07 m²
- 5. Tc,out = 87.15 °C
- 6. A = 2.209 m²