Hot oil (1.5 kg/s, cp = 2.5 kJ/(kg·K)) cools from 140 to 90 °C in a counter-flow exchanger. It heats 3 kg/s of water (cp = 4.18 kJ/(kg·K)) that enters at 20 °C. No heat is lost to the surroundings. Find the water outlet temperature Tc,out.
Heat exchangers (LMTD) worksheet with answers
A counter-flow heat exchanger has a heat transfer area of 3 m² and an overall heat transfer coefficient of 1500 W/(m²·K). The hot fluid cools from 80 to 65 °C and the cold fluid heats from 30 to 60 °C. Find the heat transfer rate Q̇.
A counter-flow heat exchanger transfers 140 kW. The hot fluid cools from 85 to 40 °C and the cold fluid heats from 20 to 70 °C. The overall heat transfer coefficient is 200 W/(m²·K). Find the heat transfer area A needed.
A counter-flow heat exchanger transfers 120 kW. The hot fluid cools from 155 to 70 °C and the cold fluid heats from 10 to 115 °C. The overall heat transfer coefficient is 300 W/(m²·K). Find the heat transfer area A needed.
Hot oil (1 kg/s, cp = 2.5 kJ/(kg·K)) cools from 80 to 60 °C in a counter-flow exchanger. It heats 2 kg/s of water (cp = 4.18 kJ/(kg·K)) that enters at 10 °C. With U = 500 W/(m²·K), find the heat transfer area A needed.
Hot oil (0.5 kg/s, cp = 2.1 kJ/(kg·K)) cools from 170 to 40 °C in a counter-flow exchanger. It heats 1.5 kg/s of water (cp = 4.18 kJ/(kg·K)) that enters at 20 °C. With U = 800 W/(m²·K), find the heat transfer area A needed.
Answer key
- 1. Tc,out = 34.95 °C
- 2. Q̇ = 120.6 kW
- 3. A = 40.28 m²
- 4. A = 8.109 m²
- 5. A = 1.763 m²
- 6. A = 2.929 m²