Hot oil (2 kg/s, cp = 2.1 kJ/(kg·K)) cools from 145 to 110 °C in a counter-flow exchanger. It heats 0.8 kg/s of water (cp = 4.18 kJ/(kg·K)) that enters at 25 °C. No heat is lost to the surroundings. Find the water outlet temperature Tc,out.
Heat exchangers (LMTD) worksheet with answers
In a parallel-flow heat exchanger the hot fluid cools from 150 to 130 °C while the cold fluid heats from 25 to 110 °C. Find the log-mean temperature difference ΔTlm.
A parallel-flow heat exchanger transfers 440 kW. The hot fluid cools from 120 to 100 °C and the cold fluid heats from 30 to 80 °C. The overall heat transfer coefficient is 300 W/(m²·K). Find the heat transfer area A needed.
A parallel-flow heat exchanger transfers 260 kW. Its heat transfer area is 20 m². The hot fluid cools from 90 to 70 °C and the cold fluid heats from 25 to 50 °C. Find the overall heat transfer coefficient U.
In a counter-flow double-pipe heat exchanger, hot oil (0.2 kg/s, cp = 2.5 kJ/(kg·K)) flows in the inner tube and cools from 135 to 85 °C. Water (0.3 kg/s, cp = 4.18 kJ/(kg·K)) in the annulus enters at 25 °C. The inner tube has a diameter of 20 mm, and U = 300 W/(m²·K) is based on this diameter. Find the tube length L needed.
Hot oil (1.5 kg/s, cp = 2.3 kJ/(kg·K)) cools from 100 to 60 °C in a counter-flow exchanger. It heats 3 kg/s of water (cp = 4.18 kJ/(kg·K)) that enters at 15 °C. With U = 500 W/(m²·K), find the heat transfer area A needed.
Answer key
- 1. Tc,out = 68.96 °C
- 2. ΔTlm = 57.3 K
- 3. A = 31.51 m²
- 4. U = 340.5 W/(m²·K)
- 5. L = 17.92 m
- 6. A = 4.734 m²
Full step-by-step solutions: practise this topic on examproblems.com.