In a heat exchanger 0.3 kg/s of glycol mix (cp = 3.6 kJ/(kg·K)) is cooled from 110 to 55 °C. Find the heat transfer rate Q̇.
Heat exchangers (LMTD) worksheet with answers
In a counter-flow heat exchanger the hot fluid cools from 110 to 45 °C while the cold fluid heats from 25 to 80 °C. Find the log-mean temperature difference ΔTlm.
A parallel-flow heat exchanger transfers 330 kW. The hot fluid cools from 90 to 45 °C and the cold fluid heats from 10 to 40 °C. The overall heat transfer coefficient is 800 W/(m²·K). Find the heat transfer area A needed.
A parallel-flow heat exchanger transfers 480 kW. Its heat transfer area is 3 m². The hot fluid cools from 135 to 120 °C and the cold fluid heats from 20 to 100 °C. Find the overall heat transfer coefficient U.
In a counter-flow heat exchanger both streams have the same heat capacity rate, ṁ·cp = 3 kW/K. The hot stream enters at 155 °C and the cold stream at 30 °C. The exchanger has A = 2 m² and U = 800 W/(m²·K). Find the hot outlet temperature Th,out.
Hot oil (0.5 kg/s, cp = 2.5 kJ/(kg·K)) cools from 145 to 40 °C in a counter-flow exchanger. It heats 1 kg/s of water (cp = 4.18 kJ/(kg·K)) that enters at 10 °C. With U = 300 W/(m²·K), find the heat transfer area A needed.
Answer key
- 1. Q̇ = 59.4 kW
- 2. ΔTlm = 24.66 K
- 3. A = 15.25 m²
- 4. U = 2946 W/(m²·K)
- 5. Th,out = 111.5 °C
- 6. A = 7.367 m²