A counter-flow heat exchanger has a heat transfer area of 1.5 m² and an overall heat transfer coefficient of 200 W/(m²·K). The hot fluid cools from 85 to 50 °C and the cold fluid heats from 20 to 60 °C. Find the heat transfer rate Q̇.
Heat exchangers (LMTD) worksheet with answers
Hot oil (1.5 kg/s, cp = 2.1 kJ/(kg·K)) cools from 130 to 55 °C in a counter-flow exchanger. It heats 3 kg/s of water (cp = 4.18 kJ/(kg·K)) that enters at 15 °C. No heat is lost to the surroundings. Find the water outlet temperature Tc,out.
A counter-flow heat exchanger transfers 310 kW. The hot fluid cools from 180 to 65 °C and the cold fluid heats from 30 to 140 °C. The overall heat transfer coefficient is 1500 W/(m²·K). Find the heat transfer area A needed.
A counter-flow heat exchanger transfers 190 kW. The hot fluid cools from 165 to 75 °C and the cold fluid heats from 30 to 50 °C. The overall heat transfer coefficient is 1000 W/(m²·K). Find the heat transfer area A needed.
Hot oil (1.5 kg/s, cp = 2.1 kJ/(kg·K)) cools from 90 to 55 °C in a counter-flow exchanger. It heats 3 kg/s of water (cp = 4.18 kJ/(kg·K)) that enters at 15 °C. With U = 1000 W/(m²·K), find the heat transfer area A needed.
Hot oil (0.5 kg/s, cp = 2.1 kJ/(kg·K)) cools from 80 to 45 °C in a counter-flow exchanger. It heats 3 kg/s of water (cp = 4.18 kJ/(kg·K)) that enters at 25 °C. With U = 1000 W/(m²·K), find the heat transfer area A needed.
Answer key
- 1. Q̇ = 8.227 kW
- 2. Tc,out = 33.84 °C
- 3. A = 5.519 m²
- 4. A = 2.547 m²
- 5. A = 2.12 m²
- 6. A = 1.096 m²