In a counter-flow heat exchanger the hot fluid cools from 170 to 60 °C while the cold fluid heats from 10 to 75 °C. Find the log-mean temperature difference ΔTlm.
Heat exchangers (LMTD) worksheet with answers
In a counter-flow heat exchanger the hot fluid cools from 175 to 130 °C while the cold fluid heats from 20 to 145 °C. Find the log-mean temperature difference ΔTlm.
A counter-flow heat exchanger transfers 220 kW. The hot fluid cools from 165 to 60 °C and the cold fluid heats from 10 to 110 °C. The overall heat transfer coefficient is 500 W/(m²·K). Find the heat transfer area A needed.
A shell-and-tube heat exchanger (one shell pass, two tube passes) must transfer 160 kW. The hot fluid cools from 115 to 45 °C and the cold fluid heats from 15 to 60 °C. The LMTD correction factor for this arrangement is F = 0.88, and U = 300 W/(m²·K). Find the heat transfer area A needed.
In a counter-flow double-pipe heat exchanger, hot oil (0.8 kg/s, cp = 2.1 kJ/(kg·K)) flows in the inner tube and cools from 150 to 90 °C. Water (1.5 kg/s, cp = 4.18 kJ/(kg·K)) in the annulus enters at 15 °C. The inner tube has a diameter of 20 mm, and U = 300 W/(m²·K) is based on this diameter. Find the tube length L needed.
Steam condenses at a constant 140 °C on the outside of the tubes of a condenser with a heat transfer area of 1 m² and U = 2500 W/(m²·K). Cooling water (1.5 kg/s, cp = 4.18 kJ/(kg·K)) enters the tubes at 10 °C. Find the water outlet temperature Tc,out.
Answer key
- 1. ΔTlm = 70.11 K
- 2. ΔTlm = 61.57 K
- 3. A = 8.387 m²
- 4. A = 14.69 m²
- 5. L = 56.12 m
- 6. Tc,out = 52.75 °C