Hot oil (1 kg/s, cp = 2.1 kJ/(kg·K)) cools from 135 to 95 °C in a counter-flow exchanger. It heats 3 kg/s of water (cp = 4.18 kJ/(kg·K)) that enters at 15 °C. No heat is lost to the surroundings. Find the water outlet temperature Tc,out.
Heat exchangers (LMTD) worksheet with answers
In a counter-flow heat exchanger the hot fluid cools from 80 to 55 °C while the cold fluid heats from 15 to 50 °C. Find the log-mean temperature difference ΔTlm.
A counter-flow heat exchanger transfers 430 kW. The hot fluid cools from 130 to 30 °C and the cold fluid heats from 15 to 50 °C. The overall heat transfer coefficient is 200 W/(m²·K). Find the heat transfer area A needed.
A shell-and-tube heat exchanger (one shell pass, two tube passes) must transfer 130 kW. The hot fluid cools from 110 to 90 °C and the cold fluid heats from 20 to 55 °C. The LMTD correction factor for this arrangement is F = 0.8, and U = 300 W/(m²·K). Find the heat transfer area A needed.
Hot oil (1.5 kg/s, cp = 2.1 kJ/(kg·K)) cools from 155 to 50 °C in a counter-flow exchanger. It heats 1 kg/s of water (cp = 4.18 kJ/(kg·K)) that enters at 25 °C. With U = 500 W/(m²·K), find the heat transfer area A needed.
Hot oil (0.5 kg/s, cp = 2.5 kJ/(kg·K)) cools from 85 to 45 °C in a counter-flow exchanger. It heats 0.5 kg/s of water (cp = 4.18 kJ/(kg·K)) that enters at 25 °C. With U = 800 W/(m²·K), find the heat transfer area A needed.
Answer key
- 1. Tc,out = 21.7 °C
- 2. ΔTlm = 34.76 K
- 3. A = 55.37 m²
- 4. A = 8.709 m²
- 5. A = 18.16 m²
- 6. A = 2.293 m²
Full step-by-step solutions: practise this topic on examproblems.com.