Hot oil (2 kg/s, cp = 2.3 kJ/(kg·K)) cools from 160 to 75 °C in a counter-flow exchanger. It heats 1.5 kg/s of water (cp = 4.18 kJ/(kg·K)) that enters at 30 °C. No heat is lost to the surroundings. Find the water outlet temperature Tc,out.
Heat exchangers (LMTD) worksheet with answers
In a heat exchanger 3 kg/s of water (cp = 4.18 kJ/(kg·K)) is heated from 40 to 65 °C. Find the heat transfer rate Q̇.
A shell-and-tube heat exchanger (one shell pass, two tube passes) must transfer 650 kW. The hot fluid cools from 120 to 85 °C and the cold fluid heats from 15 to 85 °C. The LMTD correction factor for this arrangement is F = 0.9, and U = 500 W/(m²·K). Find the heat transfer area A needed.
A parallel-flow heat exchanger transfers 140 kW. The hot fluid cools from 175 to 60 °C and the cold fluid heats from 15 to 55 °C. The overall heat transfer coefficient is 1000 W/(m²·K). Find the heat transfer area A needed.
Hot oil (2 kg/s, cp = 2.3 kJ/(kg·K)) cools from 120 to 65 °C in a counter-flow exchanger. It heats 3 kg/s of water (cp = 4.18 kJ/(kg·K)) that enters at 25 °C. With U = 500 W/(m²·K), find the heat transfer area A needed.
In a counter-flow heat exchanger both streams have the same heat capacity rate, ṁ·cp = 4 kW/K. The hot stream enters at 175 °C and the cold stream at 30 °C. The exchanger has A = 5 m² and U = 500 W/(m²·K). Find the hot outlet temperature Th,out.
Answer key
- 1. Tc,out = 92.36 °C
- 2. Q̇ = 313.5 kW
- 3. A = 28.61 m²
- 4. A = 3.13 m²
- 5. A = 9.1 m²
- 6. Th,out = 119.2 °C