Hot oil (1.5 kg/s, cp = 2.3 kJ/(kg·K)) cools from 120 to 65 °C in a counter-flow exchanger. It heats 2 kg/s of water (cp = 4.18 kJ/(kg·K)) that enters at 30 °C. No heat is lost to the surroundings. Find the water outlet temperature Tc,out.
Heat exchangers (LMTD) worksheet with answers
In a parallel-flow heat exchanger the hot fluid cools from 160 to 90 °C while the cold fluid heats from 10 to 70 °C. Find the log-mean temperature difference ΔTlm.
A counter-flow heat exchanger transfers 120 kW. The hot fluid cools from 165 to 120 °C and the cold fluid heats from 25 to 105 °C. The overall heat transfer coefficient is 800 W/(m²·K). Find the heat transfer area A needed.
A counter-flow heat exchanger transfers 40 kW. The hot fluid cools from 165 to 60 °C and the cold fluid heats from 10 to 140 °C. The overall heat transfer coefficient is 200 W/(m²·K). Find the heat transfer area A needed.
In a counter-flow double-pipe heat exchanger, hot oil (0.5 kg/s, cp = 2.3 kJ/(kg·K)) flows in the inner tube and cools from 100 to 65 °C. Water (1.5 kg/s, cp = 4.18 kJ/(kg·K)) in the annulus enters at 10 °C. The inner tube has a diameter of 32 mm, and U = 250 W/(m²·K) is based on this diameter. Find the tube length L needed.
Hot oil (1.5 kg/s, cp = 2.5 kJ/(kg·K)) cools from 120 to 80 °C in a counter-flow exchanger. It heats 1.5 kg/s of water (cp = 4.18 kJ/(kg·K)) that enters at 15 °C. With U = 300 W/(m²·K), find the heat transfer area A needed.
Answer key
- 1. Tc,out = 52.7 °C
- 2. ΔTlm = 64.52 K
- 3. A = 1.969 m²
- 4. A = 5.545 m²
- 5. L = 23.45 m
- 6. A = 6.874 m²
Full step-by-step solutions: practise this topic on examproblems.com.