A proportional controller K = 3 drives the plant G(s) = 1/(s + 10) in a unity-feedback loop. A step of size 10 is applied. Find the final value of the output y(∞).
Steady-state error & PID control worksheet with answers
1.Easy
G(s) = 1/(s + 10)K = 3r = 10
y(∞) =
2.Easy
The controller C(s) = 2(s + 5)/s drives the plant G(s) = 1/(s + 2) in a unity-feedback loop. What is the system type N of the loop?
C(s) = 2(s + 5)/sG(s) = 1/(s + 2)
N =
3.Medium
A unity-feedback loop with G(s) = K/(s(s + 5)) must follow the ramp r(t) = 10t with a steady-state error of 0.2. Find the gain K.
G(s) = K/(s(s + 5))r(t) = 10tess = 0.2
K =
4.Medium
A unity-feedback loop has G(s) = K/((s + 4)(s + 10)). Find the gain K that gives a steady-state error of 10 % for a step input.
G(s) = K/((s + 4)(s + 10))ess = 10 %
K =
5.Hard
A proportional controller K = 4 drives the plant G(s) = 4/(s(s + 6)) in a unity-feedback loop. Find the percent overshoot %OS of the step response.
G(s) = 4/(s(s + 6))K = 4
%OS = %
6.Hard
A proportional controller K = 8 drives the plant G(s) = 2/(s(s + 2)) in a unity-feedback loop. Find the peak time tp of the step response.
G(s) = 2/(s(s + 2))K = 8
tp = s
Answer key
- 1. y(∞) = 2.308
- 2. N = 1
- 3. K = 250
- 4. K = 360
- 5. %OS = 2.838 %
- 6. tp = 0.8112 s