The controller C(s) = 10(s + 3)/s drives the plant G(s) = 1/(s(s + 10)) in a unity-feedback loop. What is the system type N of the loop?
Steady-state error & PID control worksheet with answers
A unity-feedback loop has the open-loop transfer function G(s) = 10/((s + 4)(s + 10)). Find the position error constant Kp.
A unity-feedback loop with G(s) = K/(s(s + 10)) must follow the ramp r(t) = 2t with a steady-state error of 0.1. Find the gain K.
The input r(t) = 2 + 2t (a step plus a ramp) is applied to a unity-feedback loop with G(s) = 2(s + 3)/(s(s + 10)). Find the steady-state error ess.
A proportional controller K = 2 drives the plant G(s) = 4/(s(s + 4)) in a unity-feedback loop. Find the percent overshoot %OS of the step response.
A proportional controller K drives the plant G(s) = 2/(s(s + 5)) in a unity-feedback loop. Find the gain K that gives the closed loop a damping ratio ζ = 0.8.
Answer key
- 1. N = 2
- 2. Kp = 0.25
- 3. K = 200
- 4. ess = 3.333
- 5. %OS = 4.321 %
- 6. K = 4.883